Targeted Expansion of Existing HVAC Systems: Zone Climate Control for the Pharmaceutical Industry
For the packaging area of a pharmaceutical company, airinotec modernized the existing HVAC system and adapted it to changing operational requirements. An existing supply air system was retained and supplemented with four additional recirculation systems. This allows individual room areas to be heated, cooled, humidified, and dehumidified as needed. The scope of the project also included expanding the refrigeration supply, installing cold and hot water piping, and automating the systems.
New Use, Changed Requirements
With the new use of the packaging area, the requirements for climate control also changed. It was necessary to specifically account for the different loads (thermal and humidity loads) in the individual room areas and to be able to control them independently of one another. The existing supply air system was therefore integrated into the new design and expanded in terms of its functions. With an air flow rate of approximately 10,000 m³/h, it continues to play a central role in treating the air supply. Four recirculation systems complement the existing system to provide individual climate control for each area.
Recirculating Air Systems for Zone-Based Climate Control
The additional recirculating air systems were installed in the mechanical room. With airflow rates ranging from approximately 6,500 to 9,500 m³/h, they provide heating, cooling, and humidification or dehumidification for their respective assigned areas. This allows the air handling to be specifically adapted to different room loads. While the existing supply air system handles the central supply, the recirculation systems enable differentiated control of the individual zones.
Air Distribution via the Suspended Ceiling
The air distribution system was integrated into the space above the suspended ceiling. The air ducts run through this space, carrying the treated air to the individual areas of the room. Swirl air outlets connected directly to the duct system handle the air supply. Exhaust air is also removed through vents in the suspended ceiling. The ceiling cavity itself serves as an air-conducting element and is thus an integral part of the air distribution concept. airinotec supplied and installed the air duct system, including air outlets, airflow regulators, and fire dampers. The scope of work also included the necessary sealing work on the fire dampers, the suspensions, and the insulation of the air ducts.
Why replace existing technology when you can expand it intelligently? With our solution, individual areas can be climate-controlled flexibly and according to need.
Refrigeration Supply and Piping Expanded
The additional HVAC system also required an expansion of the heating supply. The heating supply via a boiler was retained. The existing refrigeration system was supplemented by an additional chiller with a cooling capacity of 220 kW. The system was designed for chilled water temperatures of 6/12 °C at an outdoor temperature of 35 °C. To connect the ventilation systems, airinotec installed the chilled and hot water piping, including the necessary insulation. Energy Valves were used to regulate the airflow rates.
Automation
The automation of the systems was implemented using Siemens S7. The control logic required for system control and the corresponding function blocks were developed by airinotec and programmed specifically for this project. The associated cabling was also part of the project scope.
End-to-End Implementation
In addition to supplying the technical equipment, airinotec handled the engineering and project management, as well as construction supervision and installation of its own scope of work, through to commissioning. This ensured that all key steps—from planning to implementation—were covered within a single, integrated project scope.
Existing Technology Integrated in a Targeted Manner and System Expanded
By combining the existing supply air system with zone-controlled recirculation systems, a flexible solution was created that allows individual areas of the space to be climate-controlled according to their respective occupancy levels. The project demonstrates how an existing HVAC system can be adapted to new usage requirements without having to replace it entirely.